Skip to content
Call:1-888-551-3082 International: 1-919-443-0207 sales@servosupplier.com
Call:1-888-551-3082 International: 1-919-443-0207 sales@servosupplier.com

2ME904.90-1

Original price $2,168.31 - Original price $2,168.31
Original price
$2,168.31
$2,168.31 - $2,168.31
Current price $2,168.31
Available, Shipping Varies
The 2ME904.90-1 module by B & R Automation is engineered for advanced industrial automation, optimized for high safety and performance. Compatibility with Automation Studio version 4.2.5, Automation Runtime V3.08, SafeDESIGNER 4.2.0, and Safety Release 1.10 ensures its optimal operation. It features status indicators for easy monitoring, providing robust diagnostics via status LEDs and software. With a maximum internal cycle time of 1600 microseconds and internal I/O power consumption of 1.78 W, it promises speed and efficiency. Electrical isolation enhances safety, with isolation between channels and the bus, certified by CE standards. Safety features comply with EN ISO 13849-1:2008, achieving up to CAT 4, Performance Level e, and Diagnostic Coverage over 94%. The module adheres to multiple international safety standards, achieving SIL CL 3, with an exceptionally low Probability of Failure per Hour. Its digital inputs operate at 3.3 VDC, and the error detection time is 100 ms, ensuring reliable performance and fault detection.
30 Day Warranty
Technical Specifications
  • Manufacturer: B & R Automation
  • Model: 2ME904.90-1
  • Automation Studio Requirement: Version 4.2.5 or higher
  • Automation Runtime Requirement: V3.08 or higher
  • SafeDESIGNER Requirement: 4.2.0 or higher
  • Safety Release Requirement: 1.10 or higher
  • Internal Cycle Time: 1600 us
  • Internal I/O Power Consumption: 1.78 W
  • Electrical Isolation: Between channels and bus (not between individual channels)
  • Certification: CE
  • Safety Standards: EN ISO 13849-1:2008
  • Performance Level: PL e
  • Diagnostic Coverage: Over 94%
  • Mean Time to Dangerous Failure: 2500 years
  • Mission Time: 20 years
  • Compliance Standards: EN IEC 61508:2010, EN IEC 61511:2004, EN IEC 62061:2010
  • Safety Integrity Level: SIL CL 3
  • Safe Failure Fraction: Over 90%
  • Probability of Failure per Hour: <1*10^-10
  • Probability of Failure per Hour for openSAFETY: <1*10^-14 multiplied by number of openSAFETY packets per hour
  • Probability of Failure on Demand: <2*10^-5
  • Proof Test Interval: 20 years
  • Safe Digital Input Nominal Voltage: 3.3 VDC
  • Error Detection Time: 100 ms
  • Isolation Voltage Between Channel and Bus: 500 V_eff
  • Maximum Cable Length: 50 cm
  • Safety Categories: CAT 3 for individual input channels, CAT 4 for input channel pairs or more
  • SIL Level for Input Channels: SIL1 & SIL2

Get In Contact

Email: sales@servosupplier.com


Phone Number: 1-888-551-3082


International: 1-919-443-0207

Fax: 1-919-867-6204