KL3312-0010
The KL3312-0010 from Beckhoff supports 2 thermocouple inputs and offers IP20 protection. Part of the KL Analog Input Modules, it features a conversion time of approx. 250 ms and a resolution of 0.1°C per digit. It provides a measuring range from -100°C to +1370°C and maintains ±0.5% measurement uncertainty with 500 V electrical isolation.
The device consumes 65 mA on the K-bus and meets EN 61000-6-2/-6-4 EMC standards while operating from 0 to +55°C. It weighs approx. 70 g and mounts on a 35 mm DIN rail. It is approved to CE, UL, ATEX, and IECEx standards.